T773 Two-Wire Transmitter

Frequency Input, Isolating Field Configurable Two-Wire Transmitter – T773

Categories: ,

Product Description

T773 Two-Wire Transmitter

The T773 Two-Wire Transmitter isolating two-wire transmitter has 5 input ranges and 2 output ranges, all of which are field selectable via top-accessed DIP switches. The T773 can accept square, triangle or pulse waveforms up to 18KHz with amplitudes from 10mVrms to 35V peak-to-peak. The T773 provides 1000Vrms of transformer-coupled isolation with outputs of either 4-20mA or 10-50mA. Current outputs are in proportion to a selected frequency input.

The T773 has 30% zero “turn-up” and 80% span “turn-down” adjustments within any user-selected input range. For example, Range 3 of Table 1 specifies 0 to 2100Hz with a minimum span of 420Hz (2100Hz – 420Hz = 1680Hz, or 80%). This 80% adjustability allows the user to field calibrate the unit for the maximum range of 0 to 2100Hz down to the minimum range of 0 to 420Hz. The maximum obtainable offset is 30% of the calibrated span: a calibrated range of 0 of 1000 Hz can be offset by 300Hz (e.g., 300Hz to 1000Hz).

Application

The T773 is useful in any application requiring isolation of a 2-wire loop current from a pulse output transducer, such as a magnetic pickup or a turbine flowmeter. The output of the T773 can be used to drive a digital meter for direct display of flow or velocity, or to interface with a computer or PLC for monitoring and control applications.

The T773 is CSA approved for intrinsically safe operation in Class I, Division 1, Groups A, B, C and D hazardous locations when installed per manufacturing drawing number.

Calibration
Input Range: 1
Output Range: 4-20mA

 

  1. Open the access lid on the top of the unit (see Top View Diagram).
  2. Select the output range using switch S6. The CLOSED position selects a 10-50mA output. The OPEN position selects a 4-20mA output.
  3. Select the input range from Table 1 and configure switches S1 through S5.
  4. Determine the percent of span by the ratio of the desired maximum input to the input limit in Table 1 (e.g., 1000Hz/2100Hz = 48%).
  5. Set the step Span rotary switch to the desired percent of span (e.g., 48% = position 4).

 

Percent of Span Position
100% A
>90% 9
>80% 8
>70% 7
>60% 6
>50% 5
>40% 4
>30% 3
>20% 2

 

  1. Determine Zero turn-up % by the ratio of desired minimum input to the desired maximum input (e.g., 0/1000Hz = 0%).
  2. Set step Zero turn-up switch to offset %. (e.g., 0% = position 0).
Zero Turn-Up % Position
0% 0
>10% 1
>20% 2
>30% 3

 

  1. Connect the input to a calibrated frequency source. Connect the output loop to a voltage supply and monitor the output current (refer to the terminal wiring).
  2. Set the calibrator to the desired minimum and adjust the fine zero to obtain an output of either 4mA or 10mA.
  3. Set the calibrator to the desired maximum and adjust the fine span to obtain an output of either 20mA or 50mA. Repeat steps 9 and 10, if necessary, for maximum accuracy.

 

Note: If loop current “swings” on input ranges 1-2, close S-5 for extra filtering.

Field Mounting

The T773 is designed for installation in industrial field environments. A sealed, diecast aluminum housing protects against corrosion, moisture, dust and electrical noise such as radio-frequency (RFI) and electromagnetic (EMI) interference.

 

For protection against extreme moisture, hosedirected water (NEMA 4) or hazardous environments, use the T805 explosion-proof housing. The T805 provides a 1/2″ and 3/4″ FPT port for operation in harsh process environments. The T805 is FM and CSA certified for use in Class I, Groups B, C & D and Class II, Groups E, F & G hazardous locations.

TECHNICAL SPECIFICATION (T773)

Input 

  • Type: Capacitive coupled
  • Minimum Amplitude:
    • 105-2150Hz: 10mVrms
    • >2150Hz: 15mVrms
  • Maximum Amplitude: 35Vp-p

Impedance

  • 100-1KHz: >6k Ohms
  • >1KHz: >40k Ohms

Output Span

4-20mA/10-50mA, switch selectable

 

Minimum Output Current

3.3mA, typical

 

Maximum Output Current

  • 4-20mA: 24mA, typical
  • 10-50mA: 58mA, typical

Supply Voltage Range

  • 4-20mA: 13 to 75VDC
  • 10-50mA: 13 to 50VDC

Line Regulation

0.07% of span (13-75V)

 

Load Regulation

0.05% of span (0-3k Ohms)

 

Voltage Drop

13VDC @ 20mA

 

Stability 

  • Zero: ±0.015% of span/°C, typical,
    ±0.028%/°C, max.
  • Span: ±0.022% of span/°C, typical,
    ±0.043%/°C, max.

 

Overall Accuracy (Includes Linearity, Hysteresis, Stability)
±0.2% of adjusted span, max.

Zero Adjustability

30% “turn-up” of span

Span Adjustability

80% “turn-down” of full-scale limit (Table 1)
Repeatability

±0.05% of span

Response Time (63% response)

  • <9KHz: 500mSec.
  • >9KHz: 40mSec.

Output Ripple, P-P (% at max. input range frequency; 0% turn-down)

  • Range 1: 0.5% (18KHz)
  • Range 2: 0.5% (9KHz)
  • Range 3: 0.7% (2100Hz)
  • Range 4: 1.2% (525Hz)

Common Mode Rejection

60Hz: 97dB, DC: 120dB

  • Common Mode Range
    60Hz: 75Vrms, max.
    DC: 1KV, max.

RFI Effect (1.5W, 470MHz at 1.5 ft.)   

<1% of span error

Isolation

1000Vrms maximum input to output, input to case, output to case

Operating Temperature Range

  • 4-20mA: -40 to 80°C (-40 to 176°F)
  • 10-50mA: -40 to 60°C (-40 to 140°F)

Weight     

0.58lbs

Agency Approval   

CSA approved intrinsically safe for hazardous locations (File No. LR42272-70).

Ordering Information
1. Specify: Model: T773-0000
2. Options: U (Urethane coating)
3. Optional Custom Factory Calibration: Specify C620 with desired input and output range.
Accessories
M004 Snap-in Channel Track, 4 feet.
T902 Mounting plate for M004, includes 4″ track.
T910 Bulkhead (flat surface) Mounting plate.
T805 Side feed field-mountable housing (EP & NEMA 4 rated), uncoated (specify Option P for white polyester powder coat).
AP9046 Action Pak 24/40VDC 65mA Power Supply.
T609 24V, 600mA Loop Power Supply.
V565 3-1/2 digit remote loop-powered indicator, wide-ranging display, NEMA 4X enclosure, CSA & FM approval standard, specify Option C to house TransPak