Product Description
WV408 Signal Conditioner
WV408 Signal Conditioner
Now approved for use in Class I Div 2 Group A, B, C, D areas!
Users can now have significant labor savings over traditional protection methods because there is no need for explosion proof enclosures and conduits.
A Class I hazardous location is one in which flammable gases or vapors may be present in the air to be ignitable or explosive. (Typical applications include petroleum refineries, spray finishing areas, utility gas plants and fuel servicing areas.)
A Division 2 area is one where the flammable gases or vapors are normally not present in an explosive concentration, but could accidentally exist.
Group A is Acetylene, Group B includes Hydrogen, Group C includes Ether and Group D includes Hydrocarbons, fuels and solvents.
The Ultra SlimPak II is an exciting new line of isolating signal conditioners from Action Instruments with greater accuracy and better stability than virtually any other signal conditioners on the market today. The Ultra SlimPak II features Smart Power, which eliminates wasted power for low loop resistance loads in the current output mode.
The WV408 has both voltage and current input ranges. Four voltage input ranges (±150mV, ±1.5V, ±15V and ±150V) are DIP switch selectable. Each of these ranges has at least 95% zero and span adjustment, which, for example, would allow you to set a 0-20mV user range on the ±150mV full scale range. Two current input ranges (±2.5mA and ±25mA) are also DIP switch selectable. “Sigma- Delta” conversion produces an effective resolution of 15 bits. Both voltage and current have input accuracies of 0.015% of full scale. Outputs include 0-10V, 0-20mA and 4-20mA. The WV408 also supports reverse output.
Smart Power
The Ultra SlimPak II uses Smart Power to control its output supply. Smart Power automatically adjusts the the voltage to drive the output loop to the required current. A low impedance current loop will subsequently require less voltage than a loop with higher impedance. Previous designs provided only a single supply at the highest voltage required to drive the highest impedance load. Using Smart Power results in power savings and reduces the operating temperature of the signal conditioner.
Enhanced LED Diagnostics
Other than when executing the pushbutton calibration routine, the LEDs blink under the following conditions:
GREEN:
- Flashes at 2Hz when the input is under range.
- Flashes at 8Hz when the input is over range.
RED:
- Flashes at 2Hz when the output is under range.
- Flashes at 8Hz when the output is over range.
An Under Range condition exists when the signal is lower than the operational low value minus 6.25% of the operational span. An Over Range condition exists when the signal is higher than the operational high value plus 6.25% of the operational span.
A voltage output short circuit may cause an under range condition (RED blinking at 2Hz rate). A current output open circuit may cause an over range condition (RED blinking at an 8Hz rate).
There could be two or more LEDs blinking at the same time, which means the module has more than one error condition. Only when all error conditions have been removed, will the LEDs be back to normal (Green ON, Red and Yellow Off).
Configuring Modules
Unless otherwise specified, the factory presets the Model WV408 as follows:
Input: |
Current |
Range: |
4-20mA |
Output: |
Current |
Range: |
4-20mA |
Reverse Out: |
Off |
Remote Cal: |
Off |
For other ranges, refer to the SWITCH SETTINGS table. Reconfigure switches S1 and S2 for the desired input type and range.
- Set position 1 of S1 to ON if a WVC16 will be utilized and remote calibration capability is desired.
- Set position 2 and 3 of S1 for the desired output type.
- Set position 4 of S1 to ON for reverse output operation.
- Set positions 5-7 of S1 and positions 1and 2 of S2 for the desired input range.
It is also possible to remotely select the setpoints using an Ethernet connection and the optional WVC16 WebView Communications Interface module.
Alarms
Each module supports up to three alarms, which can be configured to support high limit, low limit and a timer for routine maintenance.
WV16 Communications Interface (Optional)
The WVC16 Communications Interface adds functionality never before found in a signal conditioning system. The WVC16 interfaces with Ultra SlimPak II devices via an internal infrared communications link (no programming required) and provides the ability to connect as many as 32 modules to the intranet, allowing the user to view process data on a near real time basis, perform data logging functions on specified modules, calibrate the signal conditioners remotely, and view diagnostic information.
The WVC16 contains a web page server and an e-mail server. Browsers supported include Internet Explorer 5 or later and Netscape Navigator 4.7 or later. The user has the ability to have setpoint trip conditions generate an email message for up to 10 recipients. The module also contains a countdown timer that can be used to notify when routine maintemaintenance is required, such as re-calibration. The internal temperature of the module can also be monitored. All memory to support the signal conditioner’s historical data, storage of the web pages and all e-mail messages is contained in the WVC16.
The WVC16 downloads a JAVA applet to the client’s computer. The applet provides access to the signal conditioner’s data, which includes the following:
- Module configuration summary
- Module configuration editing
- Diagnostic/warning status
- Alarm setup & status
- E-mail setup, editing & address book
- Process variable viewing
Calibration
The calibration procedure is contained in the Installation & Calibration Instructions document, which is available on our website (www.actionio.com). You can also obtain it by telephoning Action technical support (703- 669-1318).
Note that Custom Calibration (option C620) is available from the factory (settings MUST be within the units specifications). For a C620, specify the following:
- a) Input Type, Range & Units (mA, mV, V).
- b) Output Type, Range & Units (ma, mV, V).
- c) Reverse Output (ON/OFF)
TECHNICAL SPECIFICATION (WV408)
Inputs
- Voltage: ±150mV, ±1.5V, ±15V or ±150VDC
- Impedance: >100k Ohms
- Over voltage: 180Vrms
- Current: ±2.5mA or ±25mA
- Impedance: <75 Ohms
- Over current 170mA, protected by resetting fuse
- Over voltage: 60V
Zero & Span Adjustment
±95% of Full Scale
Input Accuracy
±0.015% of Full Scale
- Outputs Voltage: 0 to 10VDC
- Source Impedance: <10 Ohms
- Drive: 10mA
- Current:0 to 20mA
- Source Impedance: >100k Ohms
- Compliance: 20V@20mA (1k Ohms max)
Output Accuracy
±0.05% of Full Scale Local Range
Selection
By DIP switch
Response Time
100mSec (10 to 90%)
Stability
±100ppm of full scale/°C (±0.01%/°C)
CMRR
- 120dB @ DC,
- >90dB @ 60Hz, or better
Isolation
1800VDC or peak AC between input, output & power
ESD Susceptibility
Capable of IEC 801-2 level 3 (8kV)
Power
9-30VDC; 1.0W typ., 2.0W max.
Host Module Interface
IR Link
Size
DIN rail case – refer to Dimensions drawing
Operating Temperature
0 to +60°C (32 to 140°F)
Storage Temperature
-25 to +85°C (-13 to 185°F)
Operating Humidity
15% to 95% RH,non-condensing @ 45°C
Storage Humidity
90% RH, non-condensing @ 60°C for 24 hours
Agency Approvals (EMC & Safety)
CE, EN50081-1, EN50082-2, EN61010 CSA C22.2, No. 0-M91, 142-M1987 UL508