WV478 Signal Conditioner

Frequency Input Isolating Signal Conditioner – WV 478


Product Description

WV478 Signal Conditioner

WV478 Signal Conditioner

The Ultra SlimPak II is an exciting new line of isolating signal conditioners from Action Instruments with greater accuracy and better stability than virtually any other signal conditioners on the market today. The Ultra SlimPak II features Smart Power, which eliminates wasted power for low loop resistance loads in the current output mode.

The WV478 accepts a frequency of up to 10kHz, with a minimum input span of 2Hz. The input amplitude can range from 150mVp to 150Vrms.

Smart Power

The Ultra SlimPak II uses Smart Power to control its output supply. Smart Power automatically adjusts the the voltage to drive the output loop to the required current. A low impedance current loop will subsequently require less voltage than a loop with higher impedance. Previous designs provided only a single supply at the highest voltage required to drive the highest impedance load. Using Smart Power results in power savings and reduces the operating temperature of the signal conditioner.

Enhanced LED Diagnostics

Other than when executing the pushbutton calibration routine, the LEDs blink under the following conditions:

GREEN:

  • Flashes at 2Hz when the input is under range.
  • Flashes at 8Hz when the input is over range.

 

RED:

  • Flashes at 2Hz when the output is under range.
  • Flashes at8Hz when the output is over range.

An Under Range condition exists when the signal is lower than the operational low value minus 6.25% of the operational span. An Over Range condition exists when the signal is higher than the operational high value plus 6.25% of the operational span.

A voltage output short circuit may cause an under range condition (RED blinking at 2Hz rate). A current output open circuit may cause an over range condition (RED blinking at an 8Hz rate).

There could be two or more LEDs blinking at the same time, which means the module has more than one error condition. Only when all error conditions have been removed, will the LEDs be back to normal (Green ON, Red and Yellow Off).

Configuring Modules

Unless otherwise specified, the factory presets the Model WV478 as follows:

Input: Frequency
Range: 0-1000Hz
Sensitivity: Low (set at 1Vrms)
Output: DC Current
Range: 4-20mA
Remote Cal: Off

 

  1. For other ranges, refer to the SWITCH SETTINGS table. Reconfigure switches S1 and S2 for the desired input type and range.
  2. Set position 1 of S1 to ON if a WVC16 will be utilized and remote calibration capability is desired.
  3. Set position 2 and 3 of S1 for the desired output type.
  4. Set position 4 of S1 to ON for reverse output operation.
  5. Set position 4 of S1 to ON for reverse output operation.

 

It is also possible to remotely select the setpoints using an Ethernet connection and the optional WVC16 WebView Communications Interface module.

Alarms

When used with the optional WVC16 communications module, the WV478 supports up to 3 alarms, which can be configured as high limit, low limit and a timer for routine maintenance.

WV16 Communications Interface (Optional)

The WVC16 Communications Interface adds functionality never before found in a signal conditioning system. The WVC16 interfaces with Ultra SlimPak II devices via an internal infrared communications link (no programming required) and provides the ability to connect as many as 32 modules to the intranet, allowing the user to view process data on a near real time basis, perform data logging functions on specified modules, calibrate the signal conditioners remotely, and view diagnostic information.

The WVC16 contains a web page server and an e-mail server. Browsers supported include Internet Explorer 5 or later and Netscape Navigator 4.7 or later. The user has the ability to have setpoint trip conditions generate an email message for up to 10 recipients. The module also contains a countdown timer that can be used to notify when routine maintenance is required, such as re-calibration. The internal temperature of the module can also be monitored. All memory to support the signal conditioner’s historical data, storage of the web pages and all e-mail messages is contained in the WVC16.

The WVC16 downloads a JAVA applet to

the client’s computer. The applet provides access to the signal conditioner’s data, which includes the following:

  • Module configuration summary
  • Module configuration editing
  • Diagnostic/warning status
  • Alarm setup & status
  • E-mail setup, editing & address book
  • Process variable viewing
Calibration

The calibration procedure is contained in the Installation & Calibration Instructions document, which is available on our website (www.actionio.com). You can also obtain it by telephoning Action technical support (703- 669-1318).

Note that Custom Calibration (option C620) is available from the factory (settings MUST be within the units specifications). For a C620, specify the following:

  1. a) Input Frequency Range (for example: 0 to 5000Hz).
  2. b) Input Amplitude (for example: 2.5 Volts, Peak).
  3. c) Output Type and Range (for example: 4 to 20mA).
 TECHNICAL SPECIFICATION (WV478)

Inputs

  • Frequency Input Range 0 to 10kHz
  • Minimum Input Span 2Hz
  • Amplitude (switch selectable) Low Range: 150mVp to 50Vrms
  • High Range: 500mVp to 150Vrms

 

Outputs

  • Voltage: 0 to 10VDC
  • Source Impedance: 10 ohms
  • Drive: 10mA
  • Current: 0 to 20mA
  • Source Impedance: >100k ohms
  • Compliance: 20V@20mA (1k ohms max)

 

Output Accuracy

±0.05% of full scale local range

 

Response Time

100mSec (10-90%) typical

 

Stability

±100ppm of full scale/°C (±0.01%/°C)

 

CMRR

  • 60Hz: >90dB
  • DC: >120dB

Isolation

Input to Output to Power: 1800VDC

 

ESD Susceptibility

Capable of meeting IEC801-2 level 3 (8kV)

 

Power

  • 9 to 30VDC
  • 1W typical, 2W maximum

 

Host Module Interface

IR Link

 

Size

DIN rail case – refer to Dimensions drawing

 

Temperature Range

  • Operating: 0°C to 60°C (32°F to 140°F)
  • Storage: -25°C to 85°C (-13°F to 185°F)

 

Humidity Range

  • Operating: 15% to 95% RHNC @ 45°C
  • Storage: 90% RHNC @60°C for 24 hrs

 

Agency Approvals (EMC & Safety)

CE, EN50081-1, EN50082-2, EN61010 CSA C22.2, No. 0-M91, 142-M1987 UL508

Ordering Information
1. Specify: Model: WV478-2000
2. Optional Custom Factory Calibration (specify C620, see required settings under “Calibration”)
3. Accessories.
Accessories
All WV Series modules will mount on standard TS35 (model MD03) DIN rail. In addition, the following accessories are available:
WVC16 Communications Interface
MD03 TS35 x 7.5 DIN Rail (2 meters)
WV905 24VDC Power Supply (0.5 Amp)
H910 24VDC Power Supply (1 Amp)
H915 24VDC Power Supply (2.3 Amp)
MB03 End Bracket for MD03
C650 Utility software for WVC16