Product Description
WV905 Power Supply
The WV905 power supply can be used to operate most 24VDC instruments, including Action’s Ultra SlimPak II, Ultra SlimPak, and ActionI/Q models. The WV905 will operate on input voltages ranging from 85 to 265VAC or 120 to 300VDC. The 24VDC, 0.5A output has overcurrent shutdown with automatic restart and thermal shutdown. The input is proteccted by fuse, a thermistor for inrush current protection, and a varistor for over voltage.
The WV905 is the perfect power source for Ultra SlimPak II signal conditioners and alarm units. The integrated power jumping system makes short work of connecting power, eliminating the need to “daisychain” power wires.
- Module configuration summary
- Module configuration editing
- Diagnostic/warning status
- Alarm setup & status
- E-mail setup, editing & address book
- Process variable viewing
- Data logging capabilities
All memory to support the signal conditioner’s historical data is battery backed. The web pages and all email messages are stored in non-volatile memory.
Input Voltage
- Typical: 115 to 239VAC, ±10%, 50/60Hz
- Minimum:85VAC, 120VDC
- Maximum: 265VAC, 300VDC
Input Current
- @115VAC: 250mArms, ±20%
- @230VAC: 150mArms, ±20%
- @125VDC: 125mA, ±20%
- @250VDC: 65mA, ±20%
Output Voltage
24VDC
Maximum Output Current
0.5A
Input Protection
- Fuse: 2A slowblow (internal)
- Inrush Current: Thermistor
- Over Voltage: Varistor
Switching Frequency
100kHz
Efficiency @ Maximum Load
79%
Maximum Ripple
0.1%
Load Regulation
0.2% (10% to 100% Load)
Line Regulation
0.2% (85VAC to 265VAC In)
Overload Protection
Over current shutdown with automatic restart plus thermal shutdown
Maximum Load Capacitance on Output
5.000uF
Hold Time
(full output current after loss of input)
- @115VAC: 14ms
- @230VAC: 70ms
Isolation
- Input to Output: 3kV
- Input/Output to Rail: 4kV
- Input to Ground: 1.5kV
- Output to Ground: 500V
Wire Size
26-12AWG (0.1 to 4.0mm2)
Operating Temperature
-20°C to +50°C (-4°F to 122°F)
Storage Temperature
-40°C to +85°C (-40°F to 185°F)
Operating Humidity
20% to 85% RHNC @ 45°C
Storage Humidity
20% to 90% RHNC @ 60°C for 24 hours
Size
DIN rail case – refer to Dimensions drawing
Agency Approvals
UL, CSA, CE mark